Usage Area |
Indoor Design Temperature |
Cooling Load Index |
|
Guest Room (Standard) / Bedroom |
25°C |
90–145 W/m² |
|
Study Room |
25°C |
80–145 W/m² |
|
Chinese Restaurant |
25°C |
350–465 W/m² |
|
Western Restaurant, Bar |
25°C |
230–350 W/m² |
|
Music Hall, Dance Hall, Entertainment Hall |
25°C |
260–380 W/m² |
|
Lobby |
25°C |
130–280 W/m² |
|
Corridor |
25°C |
70 W/m² |
|
Reception Hall, Main Hall |
25°C |
210–320 W/m² |
Building Type Unit Heating Load (W/m²)
|
Energy-Efficient New Residential Buildings |
60-80 |
|
Ordinary Residential Buildings |
80-100 |
|
Old Buildings |
100-150 |
|
Commercial Buildings |
120-180 |
Homes: 5–8 air changes per hour
Commercial spaces: 8–12
Special environments: adjust as needed
This approach is ideal for spaces like labs or farms where temperature control must be exact.
Allowing Margin: The Key to Ensuring Stable System Operation
|
Application Scenario |
Recommended Allowance |
Considerations |
|
Residential Buildings |
20% |
Temperature fluctuations, occasional window opening |
|
Commercial Spaces |
30% |
High foot traffic, frequent door opening |
|
Special Requirements Areas |
40% |
High demand for constant temperature, no tolerance for fluctuations |
When selecting fan coil units, a 20%-30% capacity allowance is recommended to:
Handle extreme weather conditions
Accommodate usage variations (ventilation/occupancy)
Compensate for long-term system degradation
This approach ensures reliable performance, extends equipment lifespan, and maintains comfort despite higher initial investment.
Installation Method Selection:
|
Type |
Applicable Scenarios |
Characteristics |
|
Offices, Hotels, Homes |
Hidden installation, aesthetically pleasing, requires ceiling space reservation |
|
|
Horizontal Exposed fan coil |
Renovation Projects, Small Shops |
Easy installation, built-in air outlet, cost-effective |
|
Vertical Concealed fan coil |
Offices, Homes |
Can replace traditional radiators, integrated into hidden décor |
|
Vertical Exposed fan coil unit |
Workshops, Warehouses |
Flexible installation, can be placed directly on the floor for use |
|
Cassette fan coil unit |
Bank Halls, Shopping Malls |
Four-way air supply, elegant and high-end, relatively expensive |
|
Wall-Mounted fan coil unit |
Villas, Shops |
Similar to household AC, can be connected to groundwater systems |
|
Floor-Standing fan coil unit |
Large Spaces |
Similar to household units, simple installation and use |
New homes: Horizontal concealed units blend with interiors.
Renovations: Wall-mounted or exposed units are easier to install.
Commercial spaces: Floor-standing or cassette units work best in large or design-focused areas.
Special needs: Low-noise units for quiet zones; anti-corrosion units for humid spaces.
Q: How do I know the size is right?
A: It should reach the set temperature quickly without long full-load runs.
Q: Can I mix brands?
A: Not recommended. Different parameters may lower system efficiency.